Present-day high-voltage CL: installation and maintenance experience. Part 2

First part of the article

The experience of usages according to collected data, allows to carry out the objective estimation of the chosen cable design. The total amount of damages for special types of cable lines with division into damages of cable itself or damages of cable fittings (connecting and terminal boxes) are designated in the Table 4.

Table 4. The quantity of the ac voltage cable lines damages (without taking into account lines laid on seabed) within the period from 2000 up to 2005 (1).
 
 Cable type
Type of damage
 
Place of damage
cable
connec-
tion box
termina-tion box
other сom-ponent
uncertain place
Total
 
 XLPE
 internal
26
40
28
2
-
96
 external
47
13
17
2
-
79
 uncertain
3
6
5
0
-
14
 total
76
69
50
4
0
189
 
Paper + oil
 internal
21
12
11
6
-
60
 external
63
6
9
1
-
68
 uncertain
3
3
4
0
-
10
 total
77
20
24
7
0
128
polyethylene
 internal
9
1
21
0
-
31
 external
33
3
6
0
-
42
 uncertain
3
0
6
0
-
8
 total
45
4
32
0
0
81

Paper + oil

of high pressure

 internal
13
6
3
7
-
29
 external
19
7
2
7
-
35
 uncertain
1
0
1
2
-
4
 total
33
13
6
16
0
68
Gas + paper
 internal
10
1
3
1
-
15
 external
4
0
6
4
-
14
 uncertain
0
0
2
2
-
4
 total
14
1
11
7
0
33
 

EPR (ethylene-propylene rubber)

 internal
0
0
2
0
-
2
 external
4
0
0
0
-
4
 uncertain
0
0
0
0
-
0
 total
4
0
2
0
-
6
PILC (oil soaked paper)
 internal
244
9
4
1
1
269
 external
49
1
2
4
-
56
 uncertain
0
0
1
0
-
1
 total
293
10
7
6
1
316
DC (oil + paper)
 internal
0
18
0
0
-
18
 external
0
0
0
0
-
0
 uncertain
0
0
0
0
-
0
 total
0
18
0
0
0
18

AC voltage cable of uncertain design

 internal
0
0
1
0
-
1
 external
3
4
1
0
-
8
 uncertain
4
1
0
0
2
7
 total
7
6
2
0
2
16

Total quantity of damages

549
130
134
39
3
855
 

In total, within 5 years (from 2000 till 2005) it was registered 855 cases of damages in the high and ultrahigh voltage cable lines that are laid overland (without taking into account the cable laid on seabed). 316 damages are registered for cable lines with the use of cable design with oil soaked paper insulation, which is also called "traditional". But it should be noted that cables of such type are in usagefor many years and most of them already exceeded the warranty period of operation.

Besides, 189 damages are registered for cable lines with the use of cable in insulation of cross-linked polyethylene” XLPE. In addition it also should be noted that 55% of damages for the cable of this type are internal damages. In total, as to the ac voltage cables it was registered that 33% of damages were caused by internal influence, and 67% of damages caused by external factors. General data of damages during operation for the cable lines of more than 60 kV are represented in tables 4 and 5.

Table 5.Percentage of damagesthe ac voltage cable lines (without taking into account lines with cable with oil soaked insulation) with division into the types of internal and external factors and indication the places of their laying (1).
 
Voltage

Cause of damage

%% of the given type damages to the total sum of damages

trestle
soul
air
channel
overpass
underpass
sum
60-219

External – abnormal environmental conditions

0
2
0
0
0
0
2

External – other extreme conditions

0
7
2
3
1
0
10

External – mechanical damages

0
24
0
2
2
0
28
Internal
0
21
3
0
4
4
32
Total
0
54
5
2
7
4
72
220-500

External – abnormal environmental conditions

0
1
0
0
0
0
1

External – other extreme conditions

0
3
0
0
0
0
3

External – mechanical damages

0
6
0
0
1
0
7
Internal
0
13
0
1
1
2
16
Total
0
23
0
1
2
2
28
60-500
Total sum
0
77
5
3
9
6
100

For no-failure operation of the cable line it is important to provide not only the quality of cable itself, but also the quality, correct mounting and usage of cable fittings - connecting and terminal boxes, that should always be kept in mind. Therefore, the development and production of such cable fittings is obligatory in order that a possibility of error arising during its installation was minimal and performing of the operational procedures was maximally simplified. Due to such properties cable fittings fabricated by assembly technology (technologies of semi-finished goods) become more and more popular. Example of such cable box for 400 kV voltages is shown on drawing 1, and installation of cable box for 330 kV voltage in Dnepropetrovsk - on drawing number 2.
 
Damage ratios of the ac voltage cable lines based on the collected data – internal causes taking into account all registered damages are shown in the tables 6 and 7. The comparison of damage ratios for the cable itself and for cable fittings taking into account damages of connecting and termination boxes is quite interesting.
 Монтаж муфты 400 кВ
Drawing 1. Installation of cable box for 400 kV (4).
 

Table 6. Damage ratios of cable lines with elements distribution in correlation to the amount of damages for 100 km. Internal damages (1).

 
 

Line’s component

Lines with XLPE (kV) insulation

Lines with paper-oil insulation (kV)

60-219
220-500
Total
60-219
220-500
Total
Cable
0,027
0,067
0,030
0,014
0,107
0,041

Connection box

0,005
0,026
0,005
0,002
0,010
0,004

Terminal box

0,006
0,032
0,007
0,005
0,015
0,009
 Монтаж муфты на напряжение 330кВ в г. Днепропетровске
Drawing 2 – Installation of cable box for 330 kV voltage in Dnepropetrovsk.